Product data sheet
Characteristics
NSYCVF38M115PF
ClimaSys forced vent. IP54, 38m3/h, 115V,
with outlet grille and filter G2
Main
Range
ClimaSys CV
Fan
Category
Type of filter
Flow rate
Standard
Free flow rate with standard filter : 39 m3/h at 60 Hz
Free flow rate with standard filter : 38 m3/h at 50 Hz
[Us] rated supply volt-
age
75...125 V
Input voltage
115 V 50/60 Hz
Complementary
Absorbed power
3.5 W 60 Hz
3.3 W 50 Hz
[In] rated current
0.16 A 60 Hz
0.16 A 50 Hz
Noise level < at
Bearing type
40...41 dB
Ball
Height
External : 137 mm
External : 117 mm
External : 49 mm
92 x 92 mm
0.22 kg
Width
Depth
Cut-out dimensions
Product weight
Material
Injected thermoplastic (ASA PC) for outlet grille
Colour
Outlet grille : grey RAL 7035
-10...70 °C
Ambient air temperature for operation
Ambient air temperature for storage
Maximum pressure
Connections - terminals
IP degree of protection
Device composition
-40...70 °C
29 Pa flow rate 0 m³/h
Cable
IP54
1 cut-out template
1 outlet grille front
1 filter front of axial motor
2 protective grille on the front and rear surfaces
1 axial motor
Condition of use
Outside temperature must be 5 °C lower than inside temperature
Filter must be cleaned and replaced regularly
Surrounding environment must be relatively clean
Overfrequent filter replacement should be avoided
Flow rates depends on the work point, see ProClima software
Additional information
-MUST NOT be connected to a power conversion module, an inverter or UPS
type of power supply
Jun 16, 2015
1