Catalog: 1654001
Issue Date: 06.2011
Corcom Product Guide
Multipurpose Power Line RFI Filter for Emission Control
S Series
UL Recognized
CSA Certified
VDE Approved
20VS1
3VS1
S Series
Specifications
• Combines Line to Ground interference rejection
filters with additional circuitry to reduce Line to
Line noise and transients
Maximum leakage current each Line to Ground:
3 & 20A
.4 mA
60A
.75 mA
1.25 mA
@120 VAC 60 Hz:
@250 VAC 50 Hz:
.7 mA
• Designed for use when equipment impedance at
RF frequencies is high
Hipot rating (one minute):
Line to Ground:
Line to Line:
2250 VDC
1450 VDC
• Effective for use with switch-mode power supplies
• Effective when used to control emissions in
equipment using SCR and T2L circuits for
compliance with FCC Part 15, Subpart J and
EN55022, Level A, down to 150kHz
Rated Voltage (max):
Operating Frequency:
Rated Current:
250 VAC
50/60 Hz
3 to 60A
Operating Ambient Temperature Range
(at rated current I ): -10°C to +40°C
r
In an ambient temperature (T ) higher than +40°C
a
Ordering Information
20 V S 6
the maximum operating current (I ) is calculated as
o
follows: I = I (85-Ta)/45
o
r
Electrical Schematics
3, 6, 10VS
Input / Output Style
1 – .250 [6.3] spade terminals
6 – Threaded bolt
LINE
LOAD
S Series
Leakage current designation
V – Standard
20VS
Current Rating
3, 6, 10, 20 or 60A
LINE
LOAD
Available Part Numbers
3VS1
6VS1
10VS1
20VS1
20VS6
60VS6
60VS
LINE
LOAD
68
Dimensions are in inches and millimeters unless otherwise specified. Values in italics
are metric equivalents. Dimensions are shown for reference purposes only.
Specifications subject to change.