REGISTER
(4x)
FACTORY
SETTING
REGISTER NAME
LOW LIMIT
HIGH LIMIT
ACCESS
COMMENTS
1 = 1 Display unit; In combination Reverse(r) and
Direct(d) modes, this defines the overlap area in
Read/Write which both OP1 and OP2 are active
(negative value) or the deadband area (positive
value).
-99(.9) or
-999 (process)
999(.9)° or
9999 (process)
96
97
Deadband/Overlap
2
2
250(.0)° or 2500
(process)
On/Off Control Hysteresis
2
Read/Write 1 = 1 Display unit
LOCKOUT PARAMETERS
Setpoint Access
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
0
0
0
0
0
0
1
1
1
1
1
1
1
1
1
1
2
2
2
0
4
4
4
4
4
4
3
3
3
3
3
3
3
3
3
3
3
3
3
3
0
1
1
1
1
0
1
1
1
1
3
1
1
1
1
1
2
2
2
0
Read/Write 0 = dISP, 1 = ParA, 2 = HIdE, 3 = LOC, 4 = dSPr
Read/Write 0 = dISP, 1 = ParA, 2 = HIdE, 3 = LOC, 4 = dSPr
Read/Write 0 = dISP, 1 = ParA, 2 = HIdE, 3 = LOC, 4 = dSPr
Read/Write 0 = dISP, 1 = ParA, 2 = HIdE, 3 = LOC, 4 = dSPr
Read/Write 0 = dISP, 1 = ParA, 2 = HIdE, 3 = LOC, 4 = dSPr
Read/Write 0 = dISP, 1 = ParA, 2 = HIdE, 3 = LOC, 4 = dSPr
Read/Write 1 = ParA, 2 = HIdE, 3 = LOC
Read/Write 1 = ParA, 2 = HIdE, 3 = LOC
Read/Write 1 = ParA, 2 = HIdE, 3 = LOC
Read/Write 1 = ParA, 2 = HIdE, 3 = LOC
Read/Write 1 = ParA, 2 = HIdE, 3 = LOC
Read/Write 1 = ParA, 2 = HIdE, 3 = LOC
Read/Write 1 = ParA, 2 = HIdE, 3 = LOC
Read/Write 1 = ParA, 2 = HIdE, 3 = LOC
Read/Write 1 = ParA, 2 = HIdE, 3 = LOC
Read/Write 1 = ParA, 2 = HIdE, 3 = LOC
Read/Write 2 = HIdE, 3 = LOC
Output 1 Power Access
Output 2 Power Access
Setpoint Ramp Rate Access
PID Group Access
Controller Status (Run/Stop) Access
Output Power Offset Access
Proportional band Access
Integral time Access
Derivative time Access
Integration Default Access
Alarm 1 Value Access
Alarm 2 Value Access
Alarm 3 Value Access
Alarm Reset Access
Setpoint Select Access
Auto-Tune Start Access
Auto Control Mode Access
Control Mode Transfer Access
Deviation Value Access
Read/Write 2 = HIdE, 3 = LOC
Read/Write 2 = HIdE, 3 = LOC
Read/Write 0 = dISP, 3 = LOC
0 = Full access to display, parameter, hidden, and
configuration loops; -1 to -125 = Code necessary to
access configuration loop only; 1 to 125 = Code
121
Access Code
-125
125
0
Read/Write
necessary to access hidden and configuration loops
ALARM PARAMETERS
Alarm 1 Action
0 = No, 1 = AbHI, 2 = AbLO, 3 = AUHI, 4 = AULO,
5 = d-HI, 6 = d-Lo, 7 = b-In, 8 = b-ot, 9 = InPt,
Read/Write
131
0
18
0
10 = Ct1, 11 = Ct2, 12 = SOAK, 13 = r-UP,
14 = r-dn, 15 = rUn, 16 = HoLd, 17 = StoP, 18 = End
Read/Write 0 = Normal, 1 = Reverse
Read/Write 0 = Automatic, 1 = Latched
Read/Write 0 = No, 1 = Yes
132
133
134
135
136
Alarm 1 Annunciator
Alarm 1 Reset Mode
Alarm 1 Standby
0
0
1
1
0
0
0
1
0
Alarm 1 Value
-999
0
9999
1
100
0
Read/Write 1 = 1 Display unit
Input Fail Alarm 1 Action
Read/Write 0 = Off; 1 = On
0 = No, 1 = AbHI, 2 = AbLO, 3 = AUHI, 4 = AULO,
5 = d-HI, 6 = d-Lo, 7 = b-In, 8 = b-ot, 9 = InPt,
10 = Ct1, 11 = Ct2, 12 = SOAK, 13 = r-UP,
137
Alarm 2 Action
0
18
0
Read/Write
14 = r-dn, 15 = rUn, 16 = HoLd, 17 = StoP, 18 = End
Read/Write 0 = Normal, 1 = Reverse
Read/Write 0 = Automatic, 1 = Latched
Read/Write 0 = No, 1 = Yes
138
139
140
141
142
Alarm 2 Annunciator
Alarm 2 Reset Mode
Alarm 2 Standby
0
0
1
1
0
0
0
1
0
Alarm 2 Value
-999
0
9999
1
200
0
Read/Write 1 = 1 Display unit
Input Fail Alarm 2 Action
Read/Write 0 = Off; 1 = On
0 = No, 1 = AbHI, 2 = AbLO, 3 = AUHI, 4 = AULO,
5 = d-HI, 6 = d-Lo, 7 = b-In, 8 = b-ot, 9 = InPt,
10 = Ct1, 11 = Ct2, 12 = SOAK, 13 = r-UP,
143
Alarm 3 Action
0
18
0
Read/Write
14 = r-dn, 15 = rUn, 16 = HoLd, 17 = StoP, 18 = End
Read/Write 0 = Normal, 1 = Reverse
Read/Write 0 = Automatic, 1 = Latched
Read/Write 0 = No, 1 = Yes
144
145
146
147
Alarm 3 Annunciator
Alarm 3 Reset Mode
Alarm 3 Standby
Alarm 3 Value
0
0
1
1
0
0
0
1
0
-999
9999
300
Read/Write 1 = 1 Display unit
31