Data sheet  
Voltage monitoring relay CM-EFS.2  
For single-phase AC/DC voltages  
The CM-EFS.2 is an electronic voltage monitoring  
relay that provides reliable monitoring of voltages  
as well as detection of phase loss.  
All devices are available with two different terminal  
versions. You can choose between the proven  
screw connection technology (double-chamber  
cage connection terminals) and the completely  
tool-free Easy Connect Technology (Push-in  
terminals).  
Characteristics  
Monitoring of DC and AC voltages (3-600 V)  
TRMS measuring principle  
One device includes 4 measuring ranges  
Over- and undervoltage monitoring  
ON- or OFF-delay configurable  
Latching function configurable  
Threshold values for >U and <U adjustable  
Fixed hysteresis (5 %)  
Precise adjustment by front-face operating controls  
Screw connection technology or  
Easy Connect Technology available  
Housing material for highest fire protection classification  
UL 94 V-0  
Approvals  
UL 508, CAN/CSA C22.2 No.14  
A
C
GL  
(pending)  
GOST  
CB Scheme  
CCC  
D
K
E
L
RMRS  
Tool-free mounting on DIN rail as well as demounting  
Tripping delay TV adjustable (0 s; 0.1-30 s)  
1x2 c/o (SPDT) contacts (common signal) or  
2x1 c/o (SPDT) contact (separate signals for >U and <U)  
configurable  
Marks  
CE  
a
b
C-Tick  
22.5 mm (0.89 in) width  
3 LEDs for status indication  
Order data  
Voltage monitoring relay  
Type  
Rated control supply voltage Connection technology  
Measuring ranges  
Order code  
CM-EFS.2P  
CM-EFS.2S  
24-240 V AC/DC  
24-240 V AC/DC  
Push-in terminals  
3-30 V, 6-60 V, 30-300 V, 60-600 V  
3-30 V, 6-60 V, 30-300 V, 60-600 V  
1SVR 740 750 R0400  
1SVR 730 750 R0400  
Screw type terminals  
Accessories  
Type  
Description  
Order code  
ADP.01  
MAR.12  
COV.11  
Adapter for screw mounting  
1SVR 430 029 R0100  
1SVR 730 006 R0000  
1SVR 730 005 R0100  
Marker label for devices with DIP switches  
Sealable transparent cover  
Connection technology  
Maintenance free Easy Connect Technology with  
Push-in terminals  
Approved screw connection technology with  
double-chamber cage connection terminals  
Type designation CM-xxS.yyP  
Type designation CM-xxS.yyS  
Push-in terminals  
Double-chamber cage connection terminals  
Tool-free connection of rigid and flexible wires with  
wire end ferrule according to DIN 46228-1-A,  
DIN 46228-4-E  
Wire size: 2 x 0.5-1.5 mm², (2 x 20 - 16 AWG)  
Easy connection of flexible wires without wire end  
ferrule by opening the terminals  
No retightening necessary  
One operation lever for opening both connection  
terminals  
For triggering the lever and disconnecting of wires  
you can use the same tool (Screwdriver according to  
DIN ISO 2380-1 Form A 0.8 x 4 mm (0.0315 x 0.157  
in), DIN ISO 8764-1 PZ1 ø 4.5 mm (0.177 in))  
Constant spring force on terminal point independent  
of the applied wire type, wire size or ambient  
conditions (e. g. vibrations or temperature changes)  
Opening for testing the electrical contacting  
Gas-tight  
Terminal spaces for different wire sizes:  
fine-strand with/without wire end ferrule:  
1 x 0.5-2.5 mm² (2 x 20 - 14 AWG),  
2 x 0.5-1.5 mm² (2 x 20 - 16 AWG)  
rigid:  
1 x 0.5-4 mm² (1 x 20 - 12 AWG),  
2 x 0.5-2.5 mm² (2 x 20 - 14 AWG)  
One screw for opening and closing of both cages  
Pozidrive screws for pan- or crosshead screwdrivers  
according to DIN ISO 2380-1 Form A 0.8 x 4 mm  
(0.0315 x 0.157 in), DIN ISO 8764-1 PZ1 ø 4.5 mm  
(0.177 in)  
Both the Easy Connect Technology with Push-in terminals and screw connection technology with double-chamber cage  
connection terminals have the same connection geometry as well as terminal position.  
2 - Voltage monitoring relay CM-EFS.2 | Data sheet  
Functions  
Operating controls  
1
2
3
Adjustment of the threshold value >U for overvoltage  
Adjustment of the threshold value <U for undervoltage  
Indication of operational states  
U/T: green LED – control supply voltage/timing  
R: yellow LED – relay status  
1
2
U: red LED – over- / undervoltage  
4
5
6
Adjustment of the measuring range  
Adjustment of the tripping delay TV  
DIP switches (see DIP switch functions)  
3
4
5
When compared with our previous version, the  
position of the adjustment potentiometers 4 and 5  
!
have changed places.  
6
Application  
The voltage monitoring relays CM-EFS.2 are designed for use in single-phase AC and/or DC systems for the simultaneous  
monitoring of over- or undervoltages as well as detection of phase loss. Depending on the configuration, one c/o (SPDT)  
contact each or both c/o (SPDT) contacts in parallel can be used for the over- and undervoltage monitoring. The devices  
operate over an universal range of supply voltages and provide an adjustable tripping delay. Open or closed-circuit principle  
as well as ON of OFF delay tripping are configurable.  
Operating mode  
The CM-EFS.2 have 2 c/o (SPDT) contacts and include 4 measuring ranges: 3-30 V, 6-60 V, 30-300 V and 60-600 V.  
The units are adjusted with front-face operating controls. The selection of: ON-delay A or OFF-delay B, open- h or  
closed-circuit principle g, latching function ON f or OFF e and 2x1 c/o i or 1x2 c/o (SPDT) contacts j is made  
with DIP switches. Potentiometers, with direct reading scale, allow the adjustment of the threshold valuemax (>U) for  
overvoltage, the threshold valuemin (<U) for undervoltage and the tripping delay TV . The tripping delay TV is adjustable over  
a range of instantaneous to a 30 s delay. The hysteresis is fixed at 5 %. Timing is displayed by a flashing green LED labelled  
U/T.  
Data sheet | Voltage monitoring relay CM-EFS.2 - 3  
Function diagrams  
Voltage window monitoring 1x2 c/o (SPDT) contacts jON-delayed Awithout latching e  
Open-circuit principle h  
The voltage to be monitored (measured value) is applied to terminals B-C. The control supply voltage applied to terminals  
A1-A2 is displayed by the glowing green LED.  
If the measured value exceeds the threshold valuemax (>U) or drops below the threshold valuemin (<U), the tripping delay TV  
starts and the red LED glows (overvoltage), or flashes W(undervoltage) respectively.  
Timing of TV is displayed by the flashing Wgreen LED.  
When TV is complete and the measured value still exceeds the threshold valuemax minus the fixed hysteresis (5 %) or is still  
below the threshold valuemin plus the fixed hysteresis (5 %), the output relays energize and the yellow LED (relay energized)  
glows.  
If the measured value decreases below the threshold valuemax minus the fixed hysteresis (5 %) or exceeds the threshold  
valuemin plus the fixed hysteresis (5 %), the output relays de-energize and the red and yellow LEDs turn off.  
If control supply voltage is interrupted, the green LED turns off.  
Closed-circuit principle g  
The voltage to be monitored (measured value) is applied to terminals B-C. When control supply voltage is applied to  
terminals A1-A2, the output relays energize and the green and yellow LED (relays energized) glow.  
If the measured value exceeds the threshold valuemax (>U) or drops below the threshold valuemin (<U), the tripping delay TV  
starts and the red LED glows (overvoltage), or flashes W(undervoltage) respectively.  
Timing of TV is displayed by the flashing Wgreen LED.  
When TV is complete and the measured value still exceeds the threshold valuemax minus the fixed hysteresis (5 %) or is  
still below the threshold valuemin plus the fixed hysteresis (5 %), the output relays de-energize and the yellow LED (relays  
energized) turns off.  
If the measured value decreases below the threshold valuemax minus the fixed hysteresis (5 %) or exceeds the threshold  
valuemin plus the fixed hysteresis (5 %), the output relays re-energize, the yellow LED glows and the red LED turns off.  
If control supply voltage is interrupted, the output relays de-energize and the yellow and green LEDs turn off.  
A1-A2  
Thresholdmax  
Hysteresis  
Measured value  
< TV  
TV  
< TV  
Hysteresis  
Thresholdmin  
Open-circuit principle  
open  
11-14 (15-18)  
11-12 (15-16)  
21-24 (25-28)  
21-22 (25-26)  
green LED  
red LED  
yellow LED  
closed  
Closed-circuit principle  
11-14 (15-18)  
11-12 (15-16)  
21-24 (25-28)  
21-22 (25-26)  
green LED  
red LED  
yellow LED  
4 - Voltage monitoring relay CM-EFS.2 | Data sheet  
Voltage window monitoring 1x2 c/o (SPDT) contacts jOFF-delayed Bwithout latching e  
Open-circuit principle h  
The voltage to be monitored (measured value) is applied to terminals B-C. The control supply voltage applied to terminals  
A1-A2 is displayed by the glowing green LED.  
If the measured value exceeds the threshold valuemax (>U) or drops below the threshold valuemin (<U), the output relays  
energize, the yellow LED (relays energized) glows and the red LED glows (overvoltage), or flashes W(undervoltage)  
respectively.  
If the measured value decreases below the threshold valuemax minus the fixed hysteresis (5 %) or exceeds the threshold  
valuemin plus the fixed hysteresis (5 %), the tripping delay TV starts and the red LED turns off.  
Timing of TV is displayed by the flashing Wgreen LED. When TV is complete, the output relays de-energize and the  
yellow LED (relay energized) turns off.  
If control supply voltage is interrupted, the green LED turns off.  
Closed-circuit principle g  
The voltage to be monitored (measured value) is applied to terminals B-C. When control supply voltage is applied to  
terminals A1-A2, the output relays energize and the green and yellow LED (relays energized) glow.  
If the measured value exceeds the threshold valuemax (>U) or drops below the threshold valuemin (<U), the output relays de-  
energize, the yellow LED turns off and the red LED glows (overvoltage), or flashes W(undervoltage) respectively.  
If the measured value decreases below the threshold valuemax minus the fixed hysteresis (5 %) or exceeds the threshold  
valuemin plus the fixed hysteresis (5 %), the tripping delay TV starts and the red LED turns off.  
Timing of TV is displayed by the flashing Wgreen LED. When TV is complete, the output relays energize and the  
yellow LED (relay energized) glows.  
If control supply voltage is interrupted, the output relays de-energize and the yellow and green LEDs turn off.  
A1-A2  
Thresholdmax  
Hysteresis  
Measured value  
TV  
TV  
Hysteresis  
Thresholdmin  
Open-circuit principle  
open  
11-14 (15-18)  
11-12 (15-16)  
21-24 (25-28)  
21-22 (25-26)  
green LED  
red LED  
yellow LED  
closed  
Closed-circuit principle  
11-14 (15-18)  
11-12 (15-16)  
21-24 (25-28)  
21-22 (25-26)  
green LED  
red LED  
yellow LED  
Data sheet | Voltage monitoring relay CM-EFS.2 - 5  
Voltage window monitoring 1x2 c/o (SPDT) contacts jON-delayed Awith latching f  
Open-circuit principle h  
The voltage to be monitored (measured value) is applied to terminals B-C. The control supply voltage applied to terminals  
A1-A2 is displayed by the glowing green LED.  
If the measured value exceeds the threshold valuemax (>U) or drops below the threshold valuemin (<U), the tripping delay TV  
starts and the red LED glows (overvoltage), or flashes W(undervoltage) respectively.  
Timing of TV is displayed by the flashing Wgreen LED.  
When TV is complete and the measured value still exceeds the threshold valuemax minus the fixed hysteresis (5 %) or is still  
below the threshold valuemin plus the fixed hysteresis (5 %), the output relays energize and the yellow LED (relay energized)  
flashes Z.  
If the measured value decreases below the threshold valuemax minus the fixed hysteresis (5 %) or exceeds the threshold  
valuemin plus the fixed hysteresis (5 %), the red LED turns off. The output relays remain energized (latching function).  
If control supply voltage is interrupted (reset), the output relays de-energize and the yellow and green LEDs turn off.  
Closed-circuit principle g  
The voltage to be monitored (measured value) is applied to terminals B-C. When control supply voltage is applied to  
terminals A1-A2, the output relays energize and the green and yellow LED (relays energized) glow.  
If the measured value exceeds the threshold valuemax (>U) or drops below the threshold valuemin (<U), the tripping delay TV  
starts and the red LED glows (overvoltage), or flashes W(undervoltage) respectively.  
Timing of TV is displayed by the flashing Wgreen LED.  
When TV is complete and the measured value still exceeds the threshold valuemax minus the fixed hysteresis (5 %) or is  
still below the threshold valuemin plus the fixed hysteresis (5 %), the output relays de-energize and the yellow LED (relays  
energized) flashes Y.  
If the measured value decreases below the threshold valuemax minus the fixed hysteresis (5 %) or exceeds the threshold  
valuemin plus the fixed hysteresis (5 %), the red LED turns off. The output relays remain de-energized (latching function).  
If control supply voltage is interrupted (reset), the yellow and green LEDs turn off. The output relays energize again when  
control supply voltage is re-applied.  
A1-A2  
Reset  
Thresholdmax  
Hysteresis  
Measured value  
< TV  
TV  
< TV  
Hysteresis  
Thresholdmin  
Open-circuit principle  
open  
11-14 (15-18)  
11-12 (15-16)  
21-24 (25-28)  
21-22 (25-26)  
green LED  
red LED  
yellow LED  
closed  
Closed-circuit principle  
11-14 (15-18)  
11-12 (15-16)  
21-24 (25-28)  
21-22 (25-26)  
green LED  
red LED  
yellow LED  
6 - Voltage monitoring relay CM-EFS.2 | Data sheet  
Voltage window monitoring 1x2 c/o (SPDT) contacts jOFF-delayed Bwith latching f  
Open-circuit principle h  
The voltage to be monitored (measured value) is applied to terminals B-C. The control supply voltage applied to terminals  
A1-A2 is displayed by the glowing green LED.  
If the measured value exceeds the threshold valuemax (>U) or drops below the threshold valuemin (<U), the output relays  
energize, the yellow LED (relays energized) flashes Zand the red LED glows (overvoltage), or flashes W  
(undervoltage) respectively.  
If the measured value decreases below the threshold valuemax minus the fixed hysteresis (5 %) or exceeds the threshold  
valuemin plus the fixed hysteresis (5 %), the red LED turns off. The output relays remain energized (latching function).  
If control supply voltage is interrupted (reset), the output relays de-energize and the yellow and green LEDs turn off.  
Closed-circuit principle g  
The voltage to be monitored (measured value) is applied to terminals B-C. When control supply voltage is applied to  
terminals A1-A2, the output relays energize and the green and yellow LED (relays energized) glow.  
If the measured value exceeds the threshold valuemax (>U) or drops below the threshold valuemin (<U), the output relays  
de-energize, the yellow LED (relays energized) flashes Yand the red LED glows (overvoltage), or flashes W  
(undervoltage) respectively.  
If the measured value decreases below the threshold valuemax minus the fixed hysteresis (5 %) or exceeds the threshold  
valuemin plus the fixed hysteresis (5 %), the red LED turns off. The output relays remain de-energized (latching function).  
If control supply voltage is interrupted (reset), the yellow and green LEDs turn off. The output relays energize again when  
control supply voltage is re-applied.  
A1-A2  
Reset  
Thresholdmax  
Hysteresis  
Measured value  
Hysteresis  
Thresholdmin  
Open-circuit principle  
open  
11-14 (15-18)  
11-12 (15-16)  
21-24 (25-28)  
21-22 (25-26)  
green LED  
red LED  
yellow LED  
closed  
Closed-circuit principle  
11-14 (15-18)  
11-12 (15-16)  
21-24 (25-28)  
21-22 (25-26)  
green LED  
red LED  
yellow LED  
Data sheet | Voltage monitoring relay CM-EFS.2 - 7  
Voltage window monitoring 2x1 c/o (SPDT) contact iON-delayed Awithout latching e  
Open-circuit principle h  
The voltage to be monitored (measured value) is applied to terminals B-C. The control supply voltage applied to terminals  
A1-A2 is displayed by the glowing green LED.  
If the measured value exceeds the threshold valuemax (>U) or drops below the threshold valuemin (<U), the tripping delay TV  
starts and the red LED glows (overvoltage), or flashes W(undervoltage) respectively.  
Timing of TV is displayed by the flashing Wgreen LED.  
When TV is complete and the measured value still exceeds the threshold valuemax minus the fixed hysteresis (5 %) or is still  
below the threshold valuemin plus the fixed hysteresis (5 %), the output relay 1115-1216/1418 (>U), or 2125-2226/2428 (<U)  
respectively, energizes and the yellow LED (relay energized) glows.  
If the measured value decreases below the threshold valuemax minus the fixed hysteresis (5 %) or exceeds the threshold  
valuemin plus the fixed hysteresis (5 %), the output relay 1115-1216/1418 (>U), or 2125-2226/2428 (<U) respectively, de-  
energizes and the red and yellow LEDs turn off.  
If control supply voltage is interrupted, the green LED turns off.  
Closed-circuit principle g  
The voltage to be monitored (measured value) is applied to terminals B-C. When control supply voltage is applied to  
terminals A1-A2, the output relays energize and the green and yellow LED (relays energized) glow.  
If the measured value exceeds the threshold valuemax (>U) or drops below the threshold valuemin (<U), the tripping delay TV  
starts and the red LED glows (overvoltage), or flashes W(undervoltage) respectively.  
Timing of TV is displayed by the flashing Wgreen LED.  
When TV is complete and the measured value still exceeds the threshold valuemax minus the fixed hysteresis (5 %) or is still  
below the threshold valuemin plus the fixed hysteresis (5 %), the output relay 1115-1216/1418 (>U), or 2125-2226/2428 (<U)  
respectively, de-energizes and the yellow LED (relays energized) turns off.  
If the measured value decreases below the threshold valuemax minus the fixed hysteresis (5 %) or exceeds the threshold  
valuemin plus the fixed hysteresis (5 %), the output relay 1115-1216/1418 (>U), or 2125-2226/2428 (<U) respectively, re-  
energizes, the yellow LED glows and the red LED turns off.  
If control supply voltage is interrupted, the output relays de-energize and the yellow and green LEDs turn off.  
A1-A2  
Thresholdmax  
Hysteresis  
Measured value  
< TV  
TV  
< TV  
TV  
Hysteresis  
Thresholdmin  
Open-circuit principle  
open  
11-14 (15-18)  
11-12 (15-16)  
>U:  
21-24 (25-28)  
21-22 (25-26)  
<U:  
green LED  
red LED  
yellow LED  
closed  
Closed-circuit principle  
11-14 (15-18)  
>U:  
11-12 (15-16)  
21-24 (25-28)  
<U:  
21-22 (25-26)  
green LED  
red LED  
yellow LED  
8 - Voltage monitoring relay CM-EFS.2 | Data sheet  
Voltage window monitoring 2x1 c/o (SPDT) contact iOFF-delayed Bwithout latching e  
Open-circuit principle h  
The voltage to be monitored (measured value) is applied to terminals B-C. The control supply voltage applied to terminals  
A1-A2 is displayed by the glowing green LED.  
If the measured value exceeds the threshold valuemax (>U) or drops below the threshold valuemin (<U), the output relay  
1115-1216/1418 (>U), or 2125-2226/2428 (<U) respectively, energizes, the yellow LED (relays energized) glows and the red LED  
glows (overvoltage), or flashes W(undervoltage) respectively.  
If the measured value decreases below the threshold valuemax minus the fixed hysteresis (5 %) or exceeds the threshold  
valuemin plus the fixed hysteresis (5 %), the tripping delay TV starts and the red LED turns off.  
Timing of TV is displayed by the flashing Wgreen LED. When TV is complete, the output relay 1115-1216/1418 (>U), or  
2125-2226/2428 (<U) respectively, de-energizes and the yellow LED (relay energized) turns off.  
If control supply voltage is interrupted, the green LED turns off.  
Closed-circuit principle g  
The voltage to be monitored (measured value) is applied to terminals B-C. When control supply voltage is applied to  
terminals A1-A2, the output relays energize and the green and yellow LED (relays energized) glow.  
If the measured value exceeds the threshold valuemax (>U) or drops below the threshold valuemin (<U), the output relay  
1115-1216/1418 (>U), or 2125-2226/2428 (<U) respectively, de-energizes, the yellow LED turns off and the red LED glows  
(overvoltage), or flashes W(undervoltage) respectively.  
If the measured value decreases below the threshold valuemax minus the fixed hysteresis (5 %) or exceeds the threshold  
valuemin plus the fixed hysteresis (5 %), the tripping delay TV starts and the red LED turns off.  
Timing of TV is displayed by the flashing Wgreen LED. When TV is complete, the output relay 1115-1216/1418 (>U), or  
2125-2226/2428 (<U) respectively, energizes and the yellow LED (relay energized) glows.  
If control supply voltage is interrupted, the output relays de-energize and the yellow and green LEDs turn off.  
A1-A2  
Thresholdmax  
Hysteresis  
Measured value  
TV  
TV  
Hysteresis  
Thresholdmin  
Open-circuit principle  
open  
11-14 (15-18)  
11-12 (15-16)  
>U:  
21-24 (25-28)  
21-22 (25-26)  
<U:  
green LED  
red LED  
yellow LED  
closed  
Closed-circuit principle  
11-14 (15-18)  
>U:  
11-12 (15-16)  
21-24 (25-28)  
<U:  
21-22 (25-26)  
green LED  
red LED  
yellow LED  
Data sheet | Voltage monitoring relay CM-EFS.2 - 9  
Voltage window monitoring 2x1 c/o (SPDT) contact iON-delayed Awith latching f  
Open-circuit principle h  
The voltage to be monitored (measured value) is applied to terminals B-C. The control supply voltage applied to terminals  
A1-A2 is displayed by the glowing green LED.  
If the measured value exceeds the threshold valuemax (>U) or drops below the threshold valuemin (<U), the tripping delay TV  
starts and the red LED glows (overvoltage), or flashes W(undervoltage) respectively.  
Timing of TV is displayed by the flashing Wgreen LED.  
When TV is complete and the measured value still exceeds the threshold valuemax minus the fixed hysteresis (5 %) or is still  
below the threshold valuemin plus the fixed hysteresis (5 %), the output relay 1115-1216/1418 (>U), or 2125-2226/2428 (<U)  
respectively, energizes and the yellow LED (relay energized) flashes Z.  
If the measured value decreases below the threshold valuemax minus the fixed hysteresis (5 %) or exceeds the threshold  
valuemin plus the fixed hysteresis (5 %), the red LED turns off. The output relay 1115-1216/1418 (>U), or 2125-2226/2428 (<U)  
respectively, remains energized (latching function).  
If control supply voltage is interrupted (reset), the output relay 1115-1216/1418 (>U), or 2125-2226/2428 (<U) respectively, de-  
energizes and the yellow and green LEDs turn off.  
Closed-circuit principle g  
The voltage to be monitored (measured value) is applied to terminals B-C. When control supply voltage is applied to  
terminals A1-A2, the output relays energize and the green and yellow LED (relays energized) glow.  
If the measured value exceeds the threshold valuemax (>U) or drops below the threshold valuemin (<U), the tripping delay TV  
starts and the red LED glows (overvoltage), or flashes W(undervoltage) respectively.  
Timing of TV is displayed by the flashing Wgreen LED.  
When TV is complete and the measured value still exceeds the threshold valuemax minus the fixed hysteresis (5 %) or is still  
below the threshold valuemin plus the fixed hysteresis (5 %), the output relay 1115-1216/1418 (>U), or 2125-2226/2428 (<U)  
respectively, de-energizes and the yellow LED (relays energized) flashes Y.  
If the measured value decreases below the threshold valuemax minus the fixed hysteresis (5 %) or exceeds the threshold  
valuemin plus the fixed hysteresis (5 %), the red LED turns off. The output relay 1115-1216/1418 (>U), or 2125-2226/2428 (<U)  
respectively, remains de-energized (latching function).  
If control supply voltage is interrupted (reset), the yellow and green LEDs turn off. The output relays energize again when  
control supply voltage is re-applied.  
A1-A2  
Reset  
Thresholdmax  
Hysteresis  
Measured value  
< TV  
< TV  
TV  
TV  
Hysteresis  
Thresholdmin  
Open-circuit principle  
open  
11-14 (15-18)  
11-12 (15-16)  
>U:  
21-24 (25-28)  
21-22 (25-26)  
<U:  
green LED  
red LED  
yellow LED  
closed  
Closed-circuit principle  
11-14 (15-18)  
>U:  
11-12 (15-16)  
21-24 (25-28)  
<U:  
21-22 (25-26)  
green LED  
red LED  
yellow LED  
10 - Voltage monitoring relay CM-EFS.2 | Data sheet  
Voltage window monitoring 2x1 c/o (SPDT) contact iOFF-delayed Bwith latching f  
Open-circuit principle h  
The voltage to be monitored (measured value) is applied to terminals B-C. The control supply voltage applied to terminals  
A1-A2 is displayed by the glowing green LED.  
If the measured value exceeds the threshold valuemax (>U) or drops below the threshold valuemin (<U), the output relay 1115-  
1216/1418 (>U), or 2125-2226/2428 (<U) respectively, energizes, the yellow LED (relays energized) flashes Zand the red  
LED glows (overvoltage), or flashes W(undervoltage) respectively.  
If the measured value decreases below the threshold valuemax minus the fixed hysteresis (5 %) or exceeds the threshold  
valuemin plus the fixed hysteresis (5 %), the red LED turns off. The output relay 1115-1216/1418 (>U), or 2125-2226/2428 (<U)  
respectively, remains energized (latching function).  
If control supply voltage is interrupted (reset), the output relays de-energize and the yellow and green LEDs turn off.  
Closed-circuit principle g  
The voltage to be monitored (measured value) is applied to terminals B-C. When control supply voltage is applied to  
terminals A1-A2, the output relays energize and the green and yellow LED (relays energized) glow.  
If the measured value exceeds the threshold valuemax (>U) or drops below the threshold valuemin (<U), the output relay 1115-  
1216/1418 (>U), or 2125-2226/2428 (<U) respectively, de-energizes, the yellow LED (relays energized) flashes Yand the  
red LED glows (overvoltage), or flashes W(undervoltage) respectively.  
If the measured value decreases below the threshold valuemax minus the fixed hysteresis (5 %) or exceeds the threshold  
valuemin plus the fixed hysteresis (5 %), the red LED turns off. The output relay 1115-1216/1418 (>U), or 2125-2226/2428 (<U)  
respectively, remains de-energized (latching function).  
If control supply voltage is interrupted (reset), the yellow and green LEDs turn off. The output relays energize again when  
control supply voltage is re-applied.  
A1-A2  
Reset  
Thresholdmax  
Hysteresis  
Measured value  
Hysteresis  
Thresholdmin  
Open-circuit principle  
open  
11-14 (15-18)  
>U:  
11-12 (15-16)  
21-24 (25-28)  
<U:  
21-22 (25-26)  
green LED  
red LED  
yellow LED  
closed  
Closed-circuit principle  
11-14 (15-18)  
>U:  
11-12 (15-16)  
21-24 (25-28)  
<U:  
21-22 (25-26)  
green LED  
red LED  
yellow LED  
Data sheet | Voltage monitoring relay CM-EFS.2 - 11  
Electrical connection  
A1-A2  
B-C  
Rated control supply voltage  
A1  
B
1115  
1115  
2125  
Measuring ranges: 3-30 V, 6-60 V, 30-300 V, 60-600 V  
1115-1216/1418 Output contacts - open- or closed-circuit principle  
2125-2226/2428  
B
2125  
C
A1 A2 1216 1418 2226 2428  
1418  
2428  
1216  
2226  
C
A2  
Connection diagram  
DIP switches  
1
2
3
4
ON  
OFF-delay  
Position  
ON  
4
3
2
1
closed  
OFF ON-delay  
2x1 c/o  
ON  
Closed-circuit principle  
1x2 c/o  
OFF  
open  
OFF Open-circuit principle  
ON  
OFF Latching function not activated  
ON 2x1 c/o (SPDT) contact  
OFF 1x2 c/o (SPDT) contacts  
Latching function activated  
OFF = Default  
12 - Voltage monitoring relay CM-EFS.2 | Data sheet  
Technical data  
Data at Ta = 25 °C and rated values, unless otherwise indicated  
Input circuits  
Supply circuit  
A1-A2  
24-240 V AC  
Rated control supply voltage Us  
Rated control supply voltage Us tolerance  
Rated frequency  
-15...+10 %  
50/60 Hz  
Typical current / power consumption  
24 V DC 30 mA / 0.75 W  
115 V AC 17 mA / 1.9 VA  
230 V AC 11 mA / 2.6 VA  
20 ms  
Power failure buffering time  
Transient overvoltage protection  
varistors  
Measuring circuit  
Monitoring function  
Measuring method  
B-C  
Over- and undervoltage monitoring  
TRMS measuring principle  
Measuring inputs  
terminal connection B-C  
measuring range 3-30 V, 6-60 V, 30-300 V, 60-600 V  
input resistance 600 kΩ  
pulse overload capacity t < 1 s 800 V  
continuous capacity 660 V  
>U and <U adjustable within the indicated  
Threshold value  
measuring range  
10 % of the range end value  
5 % fixed  
Tolerance of the adjusted threshold value  
Hysteresis related to the threshold value  
Measuring signal frequency range  
Rated measuring signal frequency range  
Maximum response time  
DC / 15 Hz - 2 kHz  
DC / 50-60 Hz  
AC 80 ms  
DC 120 ms  
ΔU 0.5 %  
Accuracy within the rated control supply voltage tolerance  
Accuracy within the temperature range  
ΔU 0.06 % / °C  
Transient overvoltage protection  
varistors  
Timing circuit  
Time delay TV  
0 s or 0.1-30 s adjustable  
0.07 % of full scale  
-
Repeat accuracy (constant parameters)  
Tolerance of the adjusted time delay  
Accuracy within the rated control supply voltage tolerance  
Accuracy within temperature range  
Δt 0.5 %  
Δt 0.06 % / °C  
User interface  
Indication of operational states  
Control supply voltage  
U/T: green LED  
U: red LED  
V: control supply voltage applied  
W: tripping delay TV active  
Measured value  
Relay status  
V: overvoltage  
W: undervoltage  
R: yellow LED  
V: output relay energized, no latching function  
Z: output relay energized, active latching function  
Y: output relay de-energized, active latching function  
Data sheet | Voltage monitoring relay CM-EFS.2 - 13  
Output circuits  
Kind of output  
11-12/14 relay, 1st c/o (SPDT) contact  
21-22/24 relay, 2nd c/o (SPDT) contact  
1 x 2 c/o (SPDT) contacts (common signal) or  
2 x 1 c/o (SPDT) contact (separate signal for >U and  
<U) configurable  
Operating principle  
open- or closed-circuit principle configurable (open-  
circuit principle: output relays energize if the measured  
value exceeds d/ falls below cthe adjusted  
threshold value, closed-circuit principle: output relays  
de-energize if measured value exceeds d/ falls  
below cthe adjusted threshold value)  
Contact material  
AgNi  
Rated operational voltage Ue (VDE 0110, IEC/EN 60947-1)  
Minimum switching voltage / Minimum switching current  
Maximum switching voltage / Maximum switching current  
250 V  
24 V / 10 mA  
250 V AC / 4 A AC  
Rated operational current Ie  
(IEC/EN 60947-5-1)  
AC12 (resistive) at 230 V 4 A  
AC15 (inductive) at 230 V 3 A  
DC12 (resistive) at 24 V 4 A  
DC13 (inductive) at 24 V 2 A  
AC rating (UL 508)  
utilization category (Control Circuit Rating Code) B 300  
max. rated operational voltage 300 V AC  
max. continuous thermal current at B 300 5 A  
max. making/breaking 3600/360 VA  
apparent power at B 300  
Mechanical lifetime  
Electrical lifetime  
30 x 106 switching cycles  
AC12, 230 V, 4 A 0.1 x 106 switching cycles  
n/c contact 6 A fast-acting  
Maximum fuse rating to achieve  
short-circuit protection  
n/o contact 10 A fast-acting  
General data  
MTBF  
on request  
Duty time  
100 %  
Dimensions (W x H x D)  
product dimensions 22.5 x 85.6 x 103.7 mm (0.89 x 3.37 x 4.08 in)  
packaging dimensions 97 x 109 x 30 mm (3.82 x 4.29 x 1.18 in)  
Weight  
Screw connection  
technology  
Easy Connect Technology  
(Push-in)  
Net weight 0.157 kg (0.346 lb)  
Gross weight 0.179 kg (0.395 lb)  
DIN rail (IEC/EN 60715),  
0.146 kg (0.322 lb)  
0.168 kg (0.370 lb)  
Mounting  
snap-on mounting without any tool  
Mounting position  
Material of housing  
Degree of protection  
any  
UL 94 V-0  
housing IP50  
terminals IP20  
14 - Voltage monitoring relay CM-EFS.2 | Data sheet  
Electrical connection  
Screw connection  
technology  
Easy Connect  
Technology (Push-in)  
Wire size  
fine-strand with(out) 1 x 0.5-2.5 mm²  
wire end ferrule (1 x 20-14 AWG)  
2 x 0.5-1.5 mm²  
2 x 0.5-1.5 mm²  
(2 x 20-16 AWG)  
(2 x 20-16 AWG)  
rigid 1 x 0.5-4 mm²  
(1 x 20-12 AWG)  
2 x 0.5-2.5 mm²  
(2 x 20-14 AWG)  
2 x 0.5-1.5 mm²  
(2 x 20-16 AWG)  
Stripping length  
8 mm (0.32 in)  
Tightening torque  
0.6 - 0.8 Nm  
-
(5.31 - 7.08 lb.in)  
Environmental data  
Ambient temperature ranges  
operation -20...+60 °C  
storage -40...+85 °C  
55 °C, 6 cycle  
class 2  
Damp heat, cyclic (IEC 60068-2-30)  
Vibration, sinusoidal (IEC/EN 60255-21-1)  
Shock (IEC/EN 60255-21-2)  
class 2  
Isolation data  
Rated insulation voltage Ui  
supply / measuring circuit / output 600 V  
(VDE 0110, IEC/EN 60947-1, IEC/EN 60255-5)  
supply / output 1 / output 2 250 V  
supply / measuring circuit / output 6 kV 1.2/50 μs  
supply / output 1 / output 2 4 kV 1.2/50 μs  
rated insulation voltage 250 V 2.0 kV, 50 Hz  
rated insulation voltage 600 V 2.5 kV, 50 Hz  
Rated impulse withstand voltage Uimp  
(IEC/EN 60947-1, IEC/EN 60255-5)  
Test voltage between all isolated circuits  
(type test)  
Pollution degree (VDE 0110, IEC/EN 60664, IEC/EN 60255-5)  
Overvoltage category (VDE 0110, IEC/EN 60664, IEC/EN 60255-5)  
3
III  
Standards  
Product standard  
Low Voltage Directive  
EMC Directive  
IEC/EN 60255-6  
2006/95/EC  
2004/108/EC  
2002/95/EC  
RoHS Directive  
Electromagnetic compatibility  
Interference immunity to  
electrostatic discharge  
IEC/EN 61000-6-2  
IEC/EN 61000-4-2 Level 3  
radiated, radio-frequency, electromagnetic field  
electrical fast transient / burst  
surge  
IEC/EN 61000-4-3 Level 3  
IEC/EN 61000-4-4 Level 3  
IEC/EN 61000-4-5 Level 3  
IEC/EN 61000-4-6 Level 3  
conducted disturbances, induced by  
radio-frequency fields  
Interference emission  
IEC/EN 61000-6-3  
high-frequency radiated  
IEC/CISPR 22, EN 55022 Class B  
IEC/CISPR 22, EN 55022 Class B  
high-frequency conducted  
Data sheet | Voltage monitoring relay CM-EFS.2 - 15  
Technical diagrams  
Load limit curves  
V
300  
V
300  
V
200  
V
200  
resistive load  
resistive load  
100  
80  
100  
80  
60  
50  
40  
60  
50  
40  
30  
30  
20  
20  
10  
0.1  
10  
0.1  
0.2  
0.5  
1
2
4
6
10  
0.2  
0.5  
1
2
4
6
10  
I
A
I
A
AC load (resistive)  
DC load (resistive)  
1.0  
0.9  
0.8  
F
0.7  
250 V  
resistive load  
0.6  
0.5  
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0  
cos ϕ  
Derating factor F for inductive AC load  
Switching current [A]  
Contact lifetime  
16 - Voltage monitoring relay CM-EFS.2 | Data sheet  
Dimensions  
in mm and inches  
113.4 4.47”  
105.9 4.17”  
22.5 0.89”  
103.7 4.08”  
Accessories  
in mm and inches  
8
0.32”  
4.8 0.19”  
22.5 0.89”  
62.5 2.461”  
22.2  
0.874”  
4T22  
19.9  
0.783”  
front to back  
110.5 4.31”  
60 2.362”  
70 2.756”  
ADP.01 ‑ Adapter for screw mounting  
MAR.12 ‑ Marker label for devices  
with DIP switches  
COV.11 ‑ Sealable transparent cover  
Further documentation  
Document title  
Document type  
Document number  
2CDC 110 004 C020x  
1SVC 730 570 M0000  
Electronic products and relays  
CM-EFS.2  
Technical catalogue  
Instruction manual  
You can find the documentation on the internet at www.abb.com/lowvoltage -> Control Products  
-> Electronic Relays and Controls -> Single Phase Monitors  
Data sheet | Voltage monitoring relay CM-EFS.2 - 17  
Contact us  
ABB STOTZ‑KONTAKT GmbH  
P. O. Box 10 16 80  
69006 Heidelberg, Germany  
Phone: +49 (0) 6221 7 01-0  
Fax: +49 (0) 6221 7 01-13 25  
E-mail: info.desto@de.abb.com  
You can find the address of your  
local sales organisation on the  
ABB home page  
http://www.abb.com/contacts  
-> Low Voltage Products and Systems  
Note:  
We reserve the right to make technical changes  
or modify the contents of this document without  
prior notice. With regard to purchase orders, the  
agreed particulars shall prevail. ABB AG does  
not accept any responsibility whatsoever for  
potential errors or possible lack of information in  
this document.  
We reserve all rights in this document and in  
the subject matter and illustrations contained  
therein. Any reproduction, disclosure to third  
parties or utilization of its contents – in whole  
or in parts – is forbidden without prior written  
consent of ABB AG.  
Copyright© 2010 ABB  
All rights reserved  
厂商 型号 描述 页数 下载

TOSHIBA

1SV100 硅外延平面型变容二极管[ SILICON EPITAXIAL PLANAR TYPE VARIABLE CAPACITANCE DIODE ] 3 页

TOSHIBA

1SV101 变容二极管( FM调谐器应用)[ VARIABLE CAPACITANCE DIODE (FM TUNER APPLICATIONS) ] 3 页

TOSHIBA

1SV101(F) [ Diode VAR Cap Single 15V 28pF 3-Pin Mini ] 3 页

TOSHIBA

1SV102 变容二极管( AM无线电波段调整应用程序)[ VARIABLE CAPACITANCE DIODE (AM RADIO BAND TUNING APPLICATIONS) ] 3 页

TOSHIBA

1SV103 变容二极管, FM收音机波段调谐应用[ Variable Capacitance Diode, FM Radio Band Tuning Applications ] 2 页

NEC

1SV118 [ Variable Capacitance Diode, 600pF C(T), Silicon, Hyperabrupt, TO-92, 2 PIN ] 2 页

HITACHI

1SV121 硅外延平面PIN二极管的高频衰减器[ Silicon Epitaxial Planar PIN Diode for High Frequency Attenuator ] 3 页

TAYCHIPST

1SV121 硅外延平面PIN二极管[ SILICON EPITAXIAL PLANAR PIN DIODE ] 2 页

HITACHI

1SV121RX [ Pin Diode, 100V V(BR), Silicon, DO-34 ] 3 页

RENESAS

1SV121RX [ 100V, SILICON, PIN DIODE, DO-34 ] 2 页

PDF索引:

A

B

C

D

E

F

G

H

I

J

K

L

M

N

O

P

Q

R

S

T

U

V

W

X

Y

Z

0

1

2

3

4

5

6

7

8

9

IC型号索引:

A

B

C

D

E

F

G

H

I

J

K

L

M

N

O

P

Q

R

S

T

U

V

W

X

Y

Z

0

1

2

3

4

5

6

7

8

9

Copyright 2024 gkzhan.com Al Rights Reserved 京ICP备06008810号-21 京

0.155030s