Powered by
12V 100AH
XTV 121000
XTV 121000 is a general battery up to 12 years expected life in
standby service or more than 260 cycles at 100% discharge in
cycle service. XTV has a wider operating temperature range,
which makes them more suitable for the systems in harsh
conditions.
Specification
Cells Per Unit
6
Voltage Per Unit
Capacity
12
100AH @ 20hr-rate to 1.75V per cell @ 25°C(77°F)
Approx. 30.2 kg(66.6 lbs)
Weight
Maximum Discharge Current
Internal Resistance
Operating Temperature Range
800A(5sec)
Approx. 3.9mΩ
Discharge: -20°C~50°C (-4°F~122°F)
TUV Asia Pacific Ltd.
Taiwan Branch
Charge:
Storage:
-20°C~50°C (-4°F~122°F)
-15°C~40°C ( 5°F~104°F)
Nominal Operating Temperature Range 25°C±3°C (77°F±5°F)
Float Charging Voltage
Recommended Maximum Charging
Current Limit
13.5 to 13.8 VDC/unit Average at 25°C (77°F)
TUV Asia Pacific Ltd.
Taiwan Branch
30 A
Equalization and Cycle Service
Self Discharge
14.4 to 15.0 VDC/unit Average at 25°C (77°F)
CSB-manufactured VRLA
(Absorbent Glass Mat type)
batteries are UL-recognized
components under UL1989.
CSB Batteries can be stored for more than 6 months at
25°C(77°F). Please charge batteries before using. For
higher temperatures the time interval will be shorter.
Terminal
I2-Thread lead alloy recessed terminal to accept M6/M8 bolt
Polypropylene(UL 94-HB) & Flammability resistance
of (UL 94-V0) can be available upon request.
CSB is also certified by
Container Material
ISO 9001 and ISO 14001.
Dimensions :
Unit: mm (inch)
Overall Height (H)
214±2.5 (8.43±0.10)
Container height (h)
210.6±2.5 (8.29±0.10)
Length (L)
Width (W)
308.7±2.5 (12.15±0.10) 169±2.0 (6.65±0.08)
Constant Current Discharge Characteristics Unit:A (25°C,77°F)
F.V/Time
1.60V
1.67V
1.70V
1.75V
1.80V
1.85V
5MIN
371
328
309
282
243
191
10MIN
15MIN
30MIN
60MIN
67.8
67.2
66.7
65.5
63.0
59.1
90MIN
48.9
48.7
48.3
47.7
46.3
43.8
2HR
38.7
38.4
38.0
37.6
36.5
34.6
3HR
27.7
27.4
27.3
26.9
26.1
25.2
5HR
17.7
17.5
17.4
17.3
16.8
16.1
8HR
11.6
11.5
11.4
11.3
11.2
10.7
10HR
9.54
9.47
9.45
9.38
9.16
8.82
20HR
5.05
5.02
5.01
5.00
4.84
4.63
259
194
116
242
188
114
231
184
113
212
173
110
104
193
157
170
138
96.9
Constant Power Discharge Characteristics Unit:W (25°C,77°F)
F.V/Time
1.60V
1.67V
1.70V
1.75V
1.80V
1.85V
5MIN
3591
3382
3268
2932
2572
2255
10MIN
2638
2513
2445
2308
2149
1872
15MIN
2095
2029
1987
1880
1727
1546
30MIN
1307
1286
1274
1245
1192
1125
60MIN
778
90MIN
569
2HR
450
447
445
440
429
412
3HR
323
321
319
316
308
297
5HR
211
210
209
207
203
194
8HR
138
137
136
135
133
129
10HR
114
113
112
111
110
105
20HR
59.9
59.6
59.3
59.0
58.1
55.9
775
567
771
564
761
557
735
545
695
519
Ratings presented herein are subject to revision without notice. Please refer to www.csb-battery.com to confirm the latest version.