XTV series
XTV 121100 12V 110AH
Valve Regulated Lead Acid Battery
Maintenance-Free Sealed Lead Acid Battery.
Absorbent Glass Mat (AGM) technology for efficient gas recombination of up to 99%.
Design for Standby Power Applications at Extreme Temperatures
【Design Life】
【 Float Charging Voltage】
13.5 ~ 13.8 VDC/Unit at 25℃ (77℉)
【Equalization Charging Voltage 】
14.4 ~ 15.0 VDC/Unit at 25℃ (77℉)
【 Self Discharge】
Up to 12 Years in Standby Service at 25℃
Eurobat (20℃) : 10-12 years, Long Life
【 Operating Temperature Range】
Nominal Operating Temperature : 25℃(77℉)
Discharge : -20℃ ~ 50℃ (-4℉~122℉)
Charge: -20℃ ~ 50℃ (-4℉~122℉)
Storage: -15℃ ~ 40℃ (5℉~104℉)
Less than 10% after 90 days, can be stored up to 6 months at 25℃ (77℉);
Fully recharging is required before usage, and charged sooner if stored
at higher temperature than 25℃ (77℉).
Design according with IEC 60896-21/22:2004
12V (6 cells per unit)
Specification
Nominal Voltage
Nominal Capacity
110 Ah @20hr-rate to 1.75V per cell @25℃ (77℉)
Weight
Approx. 34.20 Kg (75.38lbs)
Maximum Discharge Current
Internal Resistance
Short Circuit Current
Maximum Charge Current
Terminal types
800A (5sec)
Approx. 3.60 mΩ
2648A
33A
I2 thread lead alloy terminal to accept M6 bolt
138.6 Kgf-cm / 120.3 Lbf-in / 13.58 N-m
PP (UL 94-HB) & Flame Retardant (94-V0) available upon request
Terminal hardware Torque
Container Material
Length (L)
343.0±2.5 mm
170.0±2.0 mm
213.9±2.5 mm
216.9±2.5 mm
13.50±0.10 inch
6.69±0.08 inch
8.42±0.10 inch
8.54±0.10 inch
Width (W)
Dimensions
Container Height (h)
Overall Height (H)
Constant Current Discharge Characteristics Unit: A (25℃, 77℉)
F.V/Time
1.60V
1.67V
1.70V
1.75V
1.80V
1.85V
5 MIN
425
382
364
339
289
231
10MIN
307
289
276
254
232
200
15MIN
235
30MIN
138
60MIN
78.6
77.5
77.2
75.6
72.3
67.1
90MIN
55.8
55.4
55.0
54.0
52.1
48.8
2HR
43.7
43.5
43.0
42.5
41.2
38.9
3HR
31.2
30.8
30.7
30.3
29.4
28.2
5HR
20.0
19.9
19.7
19.5
18.9
18.2
8HR
13.1
13.0
12.9
12.8
12.6
12.0
10HR
10.7
10.6
10.5
10.4
10.2
9.86
20HR
5.53
5.52
5.51
5.50
5.33
5.15
227
222
207
188
135
134
130
123
163
114
Constant Power Discharge Characteristics Unit: W (25℃, 77℉)
F.V/Time
1.60V
1.67V
1.70V
1.75V
1.80V
1.85V
5 MIN
4173
3921
3745
3384
2988
2719
10MIN
3108
2975
2914
2783
2573
2220
15MIN
2509
2418
2368
2251
2053
1834
30MIN
1543
1515
1508
1464
1411
1323
60MIN
890
90MIN
640
2HR
505
502
501
493
479
455
3HR
363
361
359
356
346
334
5HR
236
235
234
231
228
218
8HR
155
154
153
152
149
145
10HR
126
125
124
123
122
118
20HR
66.7
66.6
66.1
65.7
64.9
62.3
884
880
862
827
635
633
622
600
773
567
Please refer to the official site for the lastest rating confirmation. URL: www.csb-battery.com
Issued:
161101
Sales Offices
Recognized under UL 1989,
and certified by ISO 9001, 14001.
BUSINESS HEADQUARTERS
Tel: +886-2-2880-5600
Fax: +866-2-2888-3300
USA OFFICE
EUROPE (EMEA) OFFICE
Tel: +31(0)180-418-140
Fax: +31(0)180-418-327
TAIPEI OFFICE
Tel: +886-2-2880-5600
Fax: +866-2-2888-3300
Tel: +1-817-244-7777 / 1-(800)3-CSB-USA (272872)
Fax: +1-817-244-4445
SHENZHEN OFFICE (CHINA)
Tel: +86-755-8831-6488, 8831-6775
Fax: +86-755-8831-6075
SHANGHAI OFFICE (CHINA)
Tel: +86-21-5046-1622, 5046-0833
Fax: +86-21-5046-1046
BEIJING OFFICE (CHINA)
Tel: +86-10-5820-5336, 5820-5338
Fax: +86-10-5820-3053