Powered by
12V 110AH
XTV 121100
XTV 121100 is a general battery up to 12 years expected life in
standby service or more than 260 cycles at 100% discharge in
cycle service. XTV has a wider operating temperature range,
which makes them more suitable for the systems in harsh
conditions.
Specification
Cells Per Unit
6
Voltage Per Unit
Capacity
12
110AH @ 20hr-rate to 1.75V per cell @ 25°C(77°F)
Approx. 34.2 kg(75.4 lbs)
Weight
Maximum Discharge Current
Internal Resistance
Operating Temperature Range
800A(5sec)
Approx. 3.4mΩ
Discharge: -20°C~50°C (-4°F~122°F)
TUV Asia Pacific Ltd.
Taiwan Branch
Charge:
Storage:
-20°C~50°C (-4°F~122°F)
-15°C~40°C ( 5°F~104°F)
Nominal Operating Temperature Range 25°C±3°C (77°F±5°F)
Float Charging Voltage
Recommended Maximum Charging
Current Limit
13.5 to 13.8 VDC/unit Average at 25°C (77°F)
TUV Asia Pacific Ltd.
Taiwan Branch
33 A
Equalization and Cycle Service
Self Discharge
14.4 to 15.0 VDC/unit Average at 25°C (77°F)
CSB-manufactured VRLA
(Absorbent Glass Mat type)
batteries are UL-recognized
components under UL1989.
CSB Batteries can be stored for more than 6 months at
25°C(77°F). Please charge batteries before using. For
higher temperatures the time interval will be shorter.
Terminal
I2-Thread lead alloy recessed terminal to accept M6/M8 bolt
Polypropylene(UL 94-HB) & Flammability resistance
of (UL 94-V0) can be available upon request.
CSB is also certified by
Container Material
ISO 9001 and ISO 14001.
Dimensions :
Unit: mm (inch)
Overall Height (H)
217.3±2.0 (8.56±0.08)
Container height (h)
213.9±2.0 (8.42±0.08) 343.0±2.5 (13.50±0.10) 170.0±2.0 (6.69±0.08)
Length (L)
Width (W)
Constant Current Discharge Characteristics Unit:A (25°C,77°F)
F.V/Time
5MIN
425
382
364
339
289
231
10MIN
307
15MIN
235
30MIN
138
60MIN
78.6
77.5
77.2
75.6
72.3
67.1
90MIN
55.8
55.4
55.0
54.0
52.1
48.8
2HR
43.7
43.5
43.0
42.5
41.2
38.9
3HR
31.2
30.8
30.7
30.3
29.4
28.2
5HR
20.0
19.9
19.7
19.5
18.9
18.2
8HR
13.1
13.0
12.9
12.8
12.6
12.0
10HR
10.7
10.6
10.5
10.4
10.2
9.86
20HR
5.53
5.52
5.51
5.50
5.33
5.15
1.60V
1.67V
1.70V
1.75V
1.80V
1.85V
289
227
135
276
222
134
254
207
130
232
188
123
200
163
114
Constant Power Discharge Characteristics Unit:W (25°C,77°F)
F.V/Time
1.60V
1.67V
1.70V
1.75V
1.80V
1.85V
5MIN
4173
3921
3745
3384
2988
2719
10MIN
3108
2975
2914
2783
2573
2220
15MIN
2509
2418
2368
2251
2053
1834
30MIN
1543
1515
1508
1464
1411
1323
60MIN
90MIN
2HR
505
502
501
493
479
455
3HR
363
361
359
356
346
334
5HR
236
235
234
231
228
218
8HR
155
154
153
152
149
145
10HR
126
125
124
123
122
118
20HR
66.7
66.6
66.1
65.7
64.9
62.3
890
640
884
635
880
633
862
622
827
600
773
567
Ratings presented herein are subject to revision without notice. Please refer to www.csb-battery.com to confirm the latest version.